345/34.5 kV 300 MVA Data Center Substation
Client: Confidential
Dates: March 2026 – June 2026
Duration: 3 months
Location: Reno, Nevada, USA
The project involved a new 345/34.5 kV substation at a Nevada data center campus, interconnected to the local utility at 345 kV. Gridwise Engineering completed the Electrical and Protection & Control design, delivering the complete electrical and protection and control package. The substation is built around a four-breaker 345 kV ring bus feeding two 345/34.5 kV transformers (90/120/150 MVA), with indoor 34.5 kV gas-insulated switchgear distributing to data center feeders. Total station capacity is approximately 300 MW with N+1 redundancy, with two 345 kV lines connecting to the utility and an adjacent substation.
Highlights & Services
Electrical and protection & control detailed design, comprising the complete electrical package and the complete protection and control schematic and wiring design.
Design of a four-breaker 345 kV ring bus interconnecting two 345/34.5 kV, 90/120/150 MVA power transformers and two 345 kV transmission lines (one to NV Energy, one to Switch SUB06).
Protection and control design using SEL relays: SEL-411L dual line current differential for the 345 kV lines, SEL-487E dual-zone transformer and bus differential, SEL-351S for 345 kV breaker failure and 34.5 kV bus overcurrent protection, and SEL-751 for 34.5 kV feeder and tie protection.
Coordination with the architectural, civil, structural and transmission line design teams.
AC loading study, DC loading study, lightning protection study (NFPA 780), lighting study and bus force calculations.
SCADA and communications design (SEL RTAC, redundant fiber optic paths) and integration of all protection functions into the station data acquisition system.
Design of the Unmanned Control Enclosure (UCE) power distribution, including 480 V and 208/120 V dry-type transformers, panelboards and DC battery backup systems.